- Voltage: 90—275VAC Over-voltage
(tested to 300Vac)
- Frequency: 47-63Hz
- Peak Inrush Current: <20A
- Power Factor: 0.99 typical
- Efficiency: ~88% with 115VAC source,
50 to 100% load
- Hold-Up Time: 20mS min.
- Input Overcurrent: (internal) 20A Fuse
|
|
- Voltage: 12, 24V, 27V, 48V, 56V, 130 & 375Vdc. Custom outputs available,
consult Factory.
- Power: 1,200W
- Accuracy: ± 50mV
- Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth
- Line Regulation: Less than ±0.25%
- Load Regulation: ±1.0% from no load to full load (droop load share)
- Parallel Use: May be paralleled with other like units for increased system
output, redundant diode included
- Current Sharing: Slope program current share, (droop)
- Temperature Coefficient: < ±0.02% per°C
Acoustic Noise < 55dBA at nominal input and full load
|
|
| |
|
| |
| |
|
| |
|
|